Skip to main content

UK Safety Signs Knowledge Hub

Fire exit sign regulations UK: illumination, height, and placement

Everything you need to know to comply with the Fire Safety Order 2005 and BS EN ISO 7010 — when fire exit signs need to be illuminated, photoluminescent options, mounting heights, and how many signs you need.

By Direct Signs Team · ISO 9001 certified UK manufacturer · Updated April 2026

The short answer

UK fire exit signs are legally required under the Regulatory Reform (Fire Safety) Order 2005 along every escape route in non-domestic premises. They must comply with BS EN ISO 7010 — green rectangle with white running-man pictogram and directional arrow. They must remain visible during a power failure, achieved either via photoluminescent ("glow-in-the-dark") signs or electrically illuminated signs backed by emergency lighting. Mounting height is typically 1.7m-2.4m, placed at every change of direction along the escape route and above each final exit door. The exact specification is determined by your fire risk assessment.

Photoluminescent vs illuminated: which do I need?

Aspect Photoluminescent Electrically illuminated
How it worksAbsorbs ambient light, glows in darknessMains-powered with battery backup on failure
Cost (per sign)£10-£40£60-£200+ (plus install)
InstallStick or screw — no electricianWired in by qualified electrician
Ongoing costNone (passive)Battery replacement every 3-4 years; periodic testing
Best forSmall premises, well-lit areas, low-risk routesLarge buildings, complex escapes, high-occupancy, dim areas
LimitsNeeds ambient light to charge — unsuitable for cellars, plant roomsBattery condition critical — failed batteries = non-compliant

The legal framework

Fire exit signage in UK non-domestic premises sits at the intersection of three regulations:

  • The Regulatory Reform (Fire Safety) Order 2005 ("RRO" or "Fire Safety Order") makes the responsible person — typically the building owner, occupier, or employer — accountable for fire safety. Article 14 requires safe routes for escape and Article 15 requires emergency lighting where necessary.
  • The Health and Safety (Safety Signs and Signals) Regulations 1996 require that safety signs comply with the relevant standard — currently BS EN ISO 7010 — including escape route and fire exit signs.
  • BS 5499-4:2013 is the UK code of practice for "Safety signs — Code of practice for escape route signing". It sets out the practical guidance on placement, height, viewing distance, and how to chain signs along an escape route.

The combined effect: you must have escape route signs, they must be the right format (BS EN ISO 7010), they must be readable in normal and emergency conditions, and they must be placed where escape can actually be navigated under stress. A fire risk assessment determines the specific requirements for your premises.

Choosing illumination: photoluminescent or electrically illuminated

Both photoluminescent and electrically illuminated fire exit signs are compliant with UK regulation. The choice is driven by the fire risk assessment, which considers:

  • Building size and complexity — larger buildings with longer escape routes typically require electrically illuminated signs supported by a full emergency lighting system. Photoluminescent signs alone may not provide the consistent visibility needed.
  • Occupancy — high-occupancy buildings (offices over 60 people, hotels, hospitals, theatres) almost always need electrically illuminated signs.
  • Ambient light during normal operation — photoluminescent signs need adequate light to charge. Permanently dim areas (cellars, plant rooms, rear corridors) cannot rely on photoluminescent alone.
  • Risk profile — sleeping accommodation, healthcare settings, and premises with at-risk occupants generally trigger more stringent illumination requirements.
  • Existing emergency lighting — if a premises already has emergency lighting that adequately illuminates fire exit signs during a power failure, the signs themselves may not need to be illuminated.

Many UK buildings use a combination: photoluminescent signs as the primary wayfinding, with electrically illuminated signs at critical decision points (final exits, complex junctions) backed by emergency lighting throughout the escape route.

Mounting height and placement

BS 5499-4:2013 sets out the practical placement rules:

  • Mounting height: top edge between 1.7m and 2.4m above the floor for standard interior placement. Above doors, just above the door frame.
  • Viewing distance: sign size must be appropriate for the maximum distance from which it needs to be readable. As a rule, the sign's character height should be at least 1/200 of the maximum viewing distance. Standard sizes: 200mm × 100mm for short distances (5-10m), 400mm × 200mm for medium (10-25m), 600mm × 300mm for long (25-40m).
  • Continuous visibility: at any point on the escape route, at least one fire exit sign should be in line of sight, indicating direction to the next sign or to the final exit.
  • Final exit: a sign directly above each final exit door, both inside and (where appropriate) outside the building.
  • Junctions and direction changes: a sign at every change of direction, every junction, and at any point where the route is not immediately obvious.
  • Floor-level signs: in high-smoke-risk environments (e.g. hotels, sleeping accommodation), supplementary low-level signs at 0.15-0.45m above the floor are recommended. Smoke rises, so signs above eye level can become invisible while floor-level signs remain readable.

How many fire exit signs do I need?

There is no fixed minimum — it depends on the building. Your fire risk assessment will determine the specific count. Reference points:

  • Small office (single floor, ≈10-20 staff): 8-15 signs typically
  • Mid-size office (2-3 floors, 50-150 staff): 25-60 signs
  • Large building (warehouse, hospital, multi-storey commercial): 100s of signs, often a planned signage scheme prepared by the architect or fire engineer

Old vs new fire exit pictograms

BS EN ISO 7010 superseded the older BS 5499-1 pictograms in 2013. The current standard pictogram is the green-and-white running-man with directional arrow that most people recognise. New installations should always use the current BS EN ISO 7010 format. Existing pre-2013 signs can usually remain in place until they reach end of life or are replaced, unless a fire risk assessment specifically identifies them as inadequate.

Maintenance and inspection

Whatever solution you install, it needs to keep working. Recommended inspection intervals:

  • Photoluminescent signs: visual inspection every 6 months. Check for fading, damage, dirt accumulation that reduces light absorption. Replace if luminance has degraded.
  • Electrically illuminated signs: monthly functional test (typically by simulating a power failure for 30 seconds), annual full discharge test. Battery replacement typically every 3-4 years. Records must be kept and made available to the responsible person.
  • All signs: annual review as part of the fire risk assessment. Building changes (new partitions, repurposed rooms, blocked routes) frequently invalidate the existing signage scheme.

Browse fire exit signs

Direct Signs supplies fire exit signs across all materials and formats:

Quick answers

Fire exit sign FAQs

Are fire exit signs a legal requirement in the UK?

Yes. The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for any non-domestic premises in England and Wales to provide adequate fire exit signage along all escape routes. Equivalent laws apply in Scotland (Fire Safety (Scotland) Regulations 2006) and Northern Ireland (Fire Safety Regulations (Northern Ireland) 2010). The signs must comply with BS EN ISO 7010 — green rectangle with white running-man pictogram and directional arrow.

Do fire exit signs need to be illuminated?

Fire exit signs must remain visible during a power failure. Two compliant approaches are allowed: photoluminescent ("glow-in-the-dark") signs that absorb ambient light and glow during darkness, or electrically illuminated signs with battery backup that activates on mains failure. The choice depends on building size, occupancy, and the assessed risk in your fire risk assessment. Larger buildings, high-occupancy premises, and complex escape routes typically require both photoluminescent signs and emergency lighting.

Do fire exit signs have to be photoluminescent?

Photoluminescent fire exit signs are not always required, but they are one of the two compliant options. They are passive, low-cost, and require no electrical install or maintenance. They must be charged by adequate ambient light during normal operation, so they are unsuitable for permanently dim spaces. Most small UK premises (offices, shops, small workplaces) use photoluminescent signs as the primary solution.

What height should fire exit signs be mounted at?

BS 5499-4:2013 — the UK code of practice for safety signs — recommends fire exit signs are mounted with their top edge between 1.7m and 2.4m above the floor. The viewing distance and crowd density inform the exact height: in busy spaces, signs need to be visible above head height. Signs above doorways are typically mounted just above the door frame. Floor-level signs supplement (not replace) these in high-smoke-risk environments.

Where should fire exit signs be placed?

Fire exit signs go at every change of direction along an escape route, above each final exit door, and at any junction where the route is not immediately obvious. The principle: someone unfamiliar with the building, in the dark, possibly with smoke obscuring vision, should always have a sign in line of sight that points to the next sign or to the exit. Specific placement is determined by your fire risk assessment.

How many fire exit signs do I need?

There is no fixed minimum count — it depends on the building. Your fire risk assessment determines what is needed. As a minimum: every escape route should have signs at every change of direction and above the final exit; complex routes need additional signs to maintain a continuous chain of visibility; multi-storey buildings need signs at each floor level showing the route to the stairs. A typical small office might need 8-15 signs; a large warehouse or hospital can require hundreds.

What colour are fire exit signs?

Fire exit signs are green and white. Specifically a green rectangle (or square) with a white running-man pictogram and white directional arrow. This is the BS EN ISO 7010 standard for "safe condition" signage — green = safe option here. The colour and shape combination is universal across the UK, EU, and most of the world for fire exits and escape routes.

Can I use the old running-man fire exit signs?

BS EN ISO 7010 superseded the older BS 5499-1 pictograms in 2013. The new pictogram is more universally recognisable and is the format required for new installations. Existing pre-2013 signs can typically remain in place until they need replacement, but if you are buying new signs in 2026, choose BS EN ISO 7010 compliant products. Direct Signs supplies the current standard pictograms across all materials and sizes.

How long do photoluminescent fire exit signs glow for?

Quality photoluminescent signs glow at recognisable brightness for 30 minutes to several hours after the lights go out, depending on photoluminescent grade and the duration and intensity of prior light exposure. The brightness fades gradually. For the sign to remain useful in an emergency, it must have been adequately charged by ambient light during normal operation — typical office lighting is sufficient for most products. Signs in permanently dim areas (cellars, plant rooms) are not suitable for photoluminescent solutions.

Do I need fire exit signs in every room?

You need fire exit signs along every escape route, but not necessarily inside every room. The principle is "continuous wayfinding from anywhere in the building to the final exit". Small rooms with a single exit normally do not need an internal fire exit sign — the sign goes outside the door, on the corridor side, pointing the way out. Larger rooms with multiple exits or complex layouts may need internal signs.

Need fire exit signs for your premises?

Direct Signs is an ISO 9001 certified UK manufacturer. Photoluminescent and standard fire exit signs in stock, dispatched next day. Bespoke options for complex sites.